Laserfiche WebLink
Duke <br />+I Energy <br />shall be used to determine start time, so that the space conditions are <br />satisfied at the set occupancy time. Units shall shut off at the end of <br />occupancy hours, but have the ability to come back on using a timed override <br />algorithm. This should be used to bring units on during evening and weekend <br />hours as required. Units should be able to cycle on during unoccupied mode, <br />with the outdoor air dampers closed, if needed to maintain unoccupied set <br />points. <br />• Add VFDs to AHU1 in Building 1000: Adding variable speed drives to <br />supply and return fans provide for improved VAV system control and allow the <br />fans to use less energy than the inlet guide vanes currently installed. <br />• Separate VFD control of supply and return fan on Building 2000 <br />AHU2: An alternative would include tapering back with inlet guide vanes. <br />(Further study required). <br />• Re- balance all zones in Buildings 1000, 2000, and 3000: The box <br />retrofit should also include re- balancing of the building including setting boxes <br />to have minimum ventilation requirements as required by current ventilation <br />standards. This will ensure proper flow to the tenant spaces, and increase the <br />ease for which the building zones can be controlled. Further study will be <br />necessary to determine if demand controlled ventilation is a viable option, <br />especially in Building 3000 where CO sensors already exist. <br />• Implement control algorithm: Look at VAV box positions and do the <br />following: <br />• Reset duct static pressure set point so that the units run at the lowest <br />possible pressure to satisfy all VAV boxes <br />• Reset supply air set point when all boxes are at minimum position to <br />reduce sub - cooling of spaces <br />Note that the primary strategy is static pressure reset resulting in fan <br />energy reduction. <br />• Economizer Control: Install new controls for economizer changeover to <br />allow the three air handlers to utilize outdoor air for "free cooling" when the <br />outdoor temperature and humidity levels are lower than inside the building. <br />5.3 ECM 3: Lighting Upgrades <br />5.3.1 Interior lighting - Future ECM (to be evaluated) <br />Group Re -lamp with reduced - wattage lamps or fixtures: RCCC should <br />consider group re -lamps of existing fixtures with reduced -watt lamps and <br />high - performance ballasts. This should be completed in phases as existing <br />ballasts and lamps depreciate. Since lighting is attributed to approximately 25 <br />to 30% of the base building load, these savings can add up. We recommend <br />the following retrofits for future consideration: <br />• Retrofit 32W T8's to 25W or 28W T8 lamp and ballasts <br />• Retrofit 54W T5's to 49W T5's <br />• Down lights should be retrofit with low -watt LEDs or dimmable CFLs, <br />especially in areas with considerable daylight. <br />Daylight Control: A large amount of the building's floors receive a significant <br />amount of natural light through the abundance of windows around the facility. <br />Lights in exterior zones could be retrofitted with dimmable ballasts, and <br />wireless low voltage ambient photocell sensors. <br />Rev A 2012 -05 -15 <br />Page 23 <br />Final Draft <br />G -2 Page 347 <br />