Laserfiche WebLink
EDISON FOARD <br />PO Box 19888 <br />Charlotte. NC 28219-0888 <br />Ph: (704)329-8000 <br />RF! <br />To: Paul Bielicki <br />RFI #: 201 <br />Moseley Architects <br />Date: 6/6!2017 <br />11430 North Community House <br />Job: 16-2711 Kannapolis Middle School <br />Road <br />Phone: <br />Charlotte, NC 28277 <br />Ph: 704-540-3755 Fax: 704-540-3754 <br />CC: <br />Subject: Roof System RFA2 <br />Drawing: A10.2 Spec Section: 074113 <br />Cost Impact: TBD Schedule Impact: TBD <br />Request: Date Required: 8/912017 <br />Please clarify the roof assembly RFA2. Sections through locations where RFA2 are located direct you to details 8, 11, and 12 on <br />A5.22; those details do not indicate the materials that make up roof assembly RFA2. Furthermore. when refering to the spec section <br />for standing seam roof panels, which is the finish for RFA2; insulation, underlayment, vapor barrier. and substrate board are <br />referenced or defined. <br />Please indicate In the documents where the components making up RFA2 are called out <br />Requested by: Jerry Anderson <br />Edison Foard Inc <br />Response: <br />To confirm, the system <br />beneath the standing <br />The components for RFA2 are indicated on A10.1 seam panels will equal <br />5.5", sames as that in <br />the majority of the TPO <br />6/ 14/2017 areas. <br />Further clarification - the components for the Insulation, <br />vapor barrier, and substrate board are equivalent to those <br />components in the membrane roofing assembly and can be <br />found in that specification section. <br />Paul Bielicki <br />Answered by <br />Moseley Architects 6/12/2017 <br />Company Date <br />At�A%InKrriber 3 \n <br />F-7 Page 172 <br />